User manual
Item Description
ROCOF limit
[2]
Trip setting in Hz/s
Time to disconnect
[2]
Time limit for inverter disconnection from grid.
6.10.4.
PV Configuration
[1] [Inverter]
This setting is not available.
Note:
For PLA settings relevant for TLX CN Pro+ inverters, refer to the section
Grid Management
.
Configure the individual PV inputs here. Select:
• Individual
• Parallel
• Auto detect
By default each PV input is configured to run in auto detect mode, thus minimising PV configu-
ration errors. When selecting individual or parallel configuration, ensure the configuration corre-
sponds to the physical wiring of the inverter.
For further information, refer to the TripleLynx CN Reference Manual.
6.10.5.
Power Level Adjustment
[0] [Plant]
[Setup → Setup details]
For networks of TLX CN Pro+ inverters, plant power output level can be controlled via the Grid
Management Box as follows:
•
Configure the grid management box inputs at plant level: [Setup → Setup details]. See
the illustration
Power Level Adjustment
.
• The grid management box sends set point values for reactive power and PLA to the
master inverter.
For further information refer to the Grid Management Box Manual.
6. Setup
L00410583-01_02 51
6