User manual
6.5.
Logging
[0] [Inverter]
6.5.1.
Logging Interval
[0] [Inverter]
Configure the logging interval of the individual inverter at [Inverter → Setup → Logging].
Logging intervals:
• 1 minute
• 10 minutes
• 1 hour
Illustration 6.13: Logging Interval
Note:
Web portals support differing logging intervals. Ask the service provider.
Note:
Changes to the logging interval impact:
• logging of detailed inverter data
• inverter logging capacity
For more information, refer to the section
Logging Capacity
.
6.5.2.
Logging Capacity
[0][Inverter]
This menu displays the current logging capacity of the data log of the particular inverter.
[Inverter → Setup→ Logging]
The logging capacity of the inverter depends on the current logging interval configuration. With
a default logging interval of 10 min., the inverter can log its detailed inverter data for a maxi-
mum of 34 days. It will then start to overwrite the old data.
6.5.3.
Delete Logs
[1] [Inverter]
At security level 1, go to [Inverter → Setup → Logging] to delete the Event, production, irradia-
tion and data log of each individual inverter.
This menu is visible in inverter and group views.
Note:
Deleting a log is an unrecoverable action and data will be lost.
6.6.
Grid Management
[1] [Plant]
This menu applies to TLX CN Pro+ variants only.
6. Setup
38 L00410583-01_02