User manual

6.2.7.
Remote Access
[2] [Inverter]
As per default it is not possible to change the functional safety settings of the inverter via the
Web Server. To be able to do so, enable the remote access check mark. Note that this must be
done individually for each inverter in the system.
Illustration 6.9: Change Functional Safety Settings
The following functional safety parameters can be set here:
Rate of change of frequency, maximum amount, and time to trip
10-minute mean value of grid voltage, maximum amount, and time to trip
Modifications made to parameters at security level 2 are recorded. See the section
Change Log
.
To change other functional safety settings, refer to the TripleLynx CN Reference Manual.
6.3.
External Alarm[0] [Inverter]
6.3.1.
External Alarm
[0] [Inverter]
Illustration 6.10: External Alarm
To use this feature, connect an external notification device, e.g. a lamp to the relay output of
the TripleLynx CN Pro inverter. For further instructions on how to connect the device, refer to
the TripleLynx CN Installation Manual.
If the alarm is triggered, it will remain active for the period of time defined under 'Alarm time-
out' (the value 0 disables the time-out functionality and the alarm will sound continuously).
While the alarm is active it can be stopped at any time by pressing the 'Stop' button. The relay
output can be tested by pressing the 'Test' button.
6. Setup
L00410583-01_02 35
6