User manual
6. Setup
6.1.
Calibration
[0] [Plant, Inverter]
Configuration of individual sensors, PV arrays and environmental settings.
6.1.1.
Sensors
[0] [Plant, Inverter]
Illustration 6.1: Sensors
Item
Unit Description
Irradiation sensor scale
mV(1000 w/m
2
)
The calibration value of the irradiation sensor.
The value is usually written on a label at the back of the
sensor.
Note that this value must be entered before the inverter
will recognise that there is an irradiation sensor connec-
ted.
Irradiation sensor temp. co-
eff.
% Calibration value for internal temperature correction of
the irradiation measurement. Only used for irradiation
sensors with integrated temperature compensation.
PV temp. offset °C The temperature sensor may be calibrated using an off-
set ranging from −5.0 to 5.0 °C.
Ambient temp. offset °C The temperature sensor may be calibrated using an off-
set ranging from −5.0 to 5.0 °C.
S0 scale pulses/kWh In order to use an energy meter (S0 sensor), the scale
of the energy meter must be entered here.
For a description of which sensor to connect to the TripleLynx CN Pro, refer to the TripleLynx
CN Installation Manual.
6.1.2.
PV Array
[0] [Inverter]
The PV area and the rated PV power (STC) for the installation are defined here.
Note:
These definitions are required to calculate PV string comparison for the plant status report.
Refer to
Messaging
.
6. Setup
28 L00410583-01_02
6