Technical data

5.3. Requirements for PV Connection
Maximum Open Circuit Voltage
The maximum open circuit voltage from the PV strings must not exceed the absolute maximum
which the inverter is able to withstand. Check the specification of the open circuit voltage at the
lowest PV module operating temperature. Also check that the maximum system voltage of the
PV modules is not exceeded! During installation, the voltage should be verified before connect-
ing the PV modules to the inverter; use a category III voltmeter that can measure DC values up
to 1000 V. Special attention must be paid to thin film modules, see the section on
Thin Film
.
Nominal Operating Area
The nominal/maximum input specification per PV input and total are given in the table below:
Parameter TripleLynx CN
8 kW
TripleLynx CN
10 kW
TripleLynx CN
12.5 kW
TripleLynx CN
15 kW
Number of inputs 2 2 3 3
Nominal/maximum PV power per input 6000 W 6000 W 6000 W 6000 W
Maximum input voltage, open circuit 1000 V 1000 V 1000 V 1000 V
Maximum input current 12 A 12 A 12 A 12 A
Nominal / maximum PV power, total 8240 W 10300 W 12900 W 15500 W
Table 5.4: PV Operating Conditions
5. Requirements for Connection
L00410582-01_02 29