Installation manual
Appendix
264 of 268 Solar-Log
1000/500/200
Installation
Interconnection of Kaco Powador inverters
Figure 16: Interconnection of Kaco Powador inverters
Instructions for Powador 6400xi and 8000xi
Interconnection of Powador 6400Xi and 8000xi:
Set 1 inverter as “Master”, 2 as “Slaves”;
Read the labelling on the inverter circuit board!
Clamp the Solar-Log™ data cable to the “LOGGER” terminal strip on the
Master inverter
Also connect the inverters to each other through the “SYM” terminal strip
Connect any additional inverters through the “Logger” terminal strip
On the inverter operating display: Set the communication addresses,
numbering consecutively
On the inverter operating display: Switch “SYM Bus” to active
Powador 6400Xi and 8000xi stand-alone mode:
Set the inverter to “Slave”, irrespective of labelling on the circuit board
Clamp the Solar-Log™ data cable to the “SYM Bus” terminal strip
On the inverter operating display: Switch “SYM Bus” to inactive
On the inverter operating display:
Set the communication addresses, numbering consecutively