Installation Instructions

Danfoss Heating
19
External
Sensor
TPOne includes an optional external sensor input.
If tted select the type of external sensor:
None - No external sensor tted
Room Sensor - Remote room sensor tted. This
will take priority over the TPOne internal sensing.
Danfoss part TS2A - sold seperately
Window Sensor - Where a window sensor has
been tted the TPOne will go into standby mode
while the window is open. Window open feature
is activated 60secs after input is made open circuit.
Window open feature is deactivated 30secs after
input is made closed circuit.
Floor Limit Sensor - This allows for a thermostat
limit sensor to be set, typical application is oor
heating. If the temperature sensed by the limit
sensor exceeds the limit setting the output will be
turned o until the temperature has dropped by
2°C. A warning will be shown on the display that
the oor limit temperature has been exceeded.
Room temperature will be controlled by the
TPOne internal sensor.
The temperature set for the limit point sensor will
be determined by the type of oor.
The recommended limits are:
Tiles on chipboard and wooden oors 27°C
Carpet or vinyl on chipboard 35°C
Tiles on concrete oor 40°C
Concrete, screed, etc 45°C
Danfoss Part TS3 - sold seperately
Lockout - Where a Key lockout switch is tted
the TPOne can be forced into the standby mode
remotely. While activated none of the buttons
can be used and the TPOne will only call for heat
if room temperature falls below set frost protect
level. Lockout feature is activated 60secs after
input is made open circuit. Feature is deactivated
30secs after input is made closed circuit