Datasheet

Data Sheet SONOMETER
TM
2000 – Ultrasonic heat meter
SONO 2500 CT The flow sensor can be mounted in either
forward or return pipes. The correct direction
is indicated with an arrow on the flange or on
the body. When horizontally mounted, the max.
liquid temperature is 150 °C .
The max. liquid temperature must be reduced to
120 °C when the electronics (black enclosure) is
turned upwards. When vertically mounted, the
max. liquid temperature is also 120 °C.
The electronics (black enclosure) must not be
insulated.
The flow sensor must be filled completely with
water during measurements.
It is not necessary to use filters when using the
flow sensor. Strait pipe inlet section has to be 5
times DN.
15
DH-SMT/PL
VD.SH.A3.02 © Danfoss 08/2009