Operation Manual

5
Fix at a height of approximately 1.5m from the oor,
away from draughts or heat sources such a fan-coil
outlets, sunlight or of ce equipment.
Pipe sensor location
Fix the pipe sensor to the ow pipe using the clamping
band supplied.
Important note: It is essential that the circuit in which
the pipe sensor is located is not closed off and that
water circulates past the sensor at all times when the
system is in operation. This may require the tting of a
bypass valve between system ow and return to ensure
circulation past the sensor.
!
PS1
BYPASS
PS1
GB - Installation Instructions