Owner manual

33
Assembly
Insert adapter into thermostat neck
Design
Mount AB-QM valve on hot-water pipe
(see instruction for AB-QM)
Setting knob
Adapter
AB-QM valve
Hot-water pipe
Temperature sensor
Rubber selling for sensor
Sensor holder
Set desired setting on AB-QM
(see instruction for AB-QM)
Mounting
QT should be mounted on the AB-QM by
hand. Maximum allowed torque is 5 Nm.
Sensor installation
AB-QM is to be installed after the last
radiator in the riser of one-pipe radiator
system.
QT should be mounted on the AB-QM by
hand. Maximum allowed torque is 5 Nm.
For proper heat transfer between a heating
water pipe and the thermostat sensor, it
is very important to apply thermo paste
(included in the box) on the surfaces in
contact.
It is recommended to insulate the sensor
if the thermostat is installed in a very cold
place (< 5 °C).
Sensor itself can be mounted in any
direction. It can be mounted above or
below sensor head.
Setting
QT temperature setting depends on AB-
QM flow setting.
It is necessary to set the AB-QM to desired
setting before the thermostat is mounted.
It is recommended to set AB-QM between
30 and 70 % flow setting.
QT thermostat is set to the desired setting
by hand. When minimum or maximum
setting is required, QT setting knob is to
be moved slightly in opposite direction
to ensure optimal performance of the
thermostat.
AB-QM DN 10-20 (35-50 °C)
Temp.
setting
C]
QT Sensor setting (turns)
0 1 2 3 4 5 6
AB-QM (flow setting)
20% 38.0 40.5 43.0 45.5 48.0 50.5 53.0
30% 37.0 39.5 42.0 44.5 47.0 49.5 52.0
40% 36.0 38.5 41.0 43.5 46.0 48.5 51.0
50% 35.0 37.5 40.0 42.5 45.0 47.5 50.0
60% 34.0 36.5 39.0 41.5 44.0 46.5 49.0
70% 33.0 35.5 38.0 40.5 43.0 45.5 48.0
80% 32.0 34.5 37.0 39.5 42.0 44.5 47.0
90% 31.0 33.5 36.0 38.5 41.0 43.5 46.0
100% 30.0 32.5 35.0 37.5 40.0 42.5 45.0
Factory setting of the thermostat is 4.
AB-QM DN 25-32 (35-50 °C)
Temp.
setting
C]
QT Sensor setting (turns)
0 1 2 3 4 5 6
AB-QM (flow setting)
20% 39.5 42.0 44.5 47.0 49.5 52.0 54.5
30% 38.0 40.5 43.0 45.5 48.0 50.5 53.0
40% 36.5 39.0 41.5 44.0 46.5 49.0 51.5
50% 35.0 37.5 40.0 42.5 45.0 47.5 50.0
60% 33.5 36.0 38.5 41.0 43.5 46.0 48.5
70% 32.0 34.5 37.0 39.5 42.0 44.5 47.0
80% 30.5 33.0 35.5 38.0 40.5 43.0 45.5
90% 29.0 31.5 34.0 36.5 39.0 41.5 44.0
100% 27.5 30.0 32.5 35.0 37.5 40.0 42.5
Factory setting of the thermostat is 4.
AB-QM DN 10-20 (45-60 °C)
Temp.
setting
C]
QT Sensor setting (turns)
0 1 2 3 4 5 6
AB-QM (flow setting)
20% 48.0 50.5 53.0 55.5 58.0 60.5 63.0
30% 47.0 49.5 52.0 54.5 57.0 59.5 62.0
40% 46.0 48.5 51.0 53.5 56.0 58.5 61.0
50% 45.0 47.5 50.0 52.5 55.0 57.5 60.0
60% 44.0 46.5 49.0 51.5 54.0 56.5 59.0
70% 43.0 45.5 48.0 50.5 53.0 55.5 58.0
80% 42.0 44.5 47.0 49.5 52.0 54.5 57.0
90% 41.0 43.5 46.0 48.5 51.0 53.5 56.0
100% 40.0 42.5 45.0 47.5 50.0 52.5 55.0
Factory setting of the thermostat is 4.
AB-QM DN 25-32 (45-60 °C)
Temp.
setting
C]
QT Sensor setting (turns)
0 1 2 3 4 5 6
AB-QM (flow setting)
20% 49.5 52.0 54.5 57.0 59.5 62.0 64.5
30% 48.0 50.5 53.0 55.5 58.0 60.5 63.0
40% 46.5 49.0 51.5 54.0 56.5 59.0 61.5
50% 45.0 47.5 50.0 52.5 55.0 57.5 60.0
60% 43.5 46.0 48.5 51.0 53.5 56.0 58.5
70% 42.0 44.5 47.0 49.5 52.0 54.5 57.0
80% 40.5 43.0 45.5 48.0 50.5 53.0 55.5
90% 39.0 41.5 44.0 46.5 49.0 51.5 54.0
100% 37.5 40.0 42.5 45.0 47.5 50.0 52.5
Factory setting of the thermostat is 4.
Disposal instruction
This product should be
dismantled and its
components sorted, if
possible, in various groups
before recycling or disposal.
Always follow the local disposal
regulations.
Installation Guide Thermostatic actuator QT
Danfoss Heating VI.C6.F3.8G DH-SMT/SI
ENGLISH