Installation Guide
© Danfoss | Climate solutions | 2021.07
AN383426363919en-000101 | 4
PXE 04: Baseplate layout
PXE 04: Mounting instructions
Fig. 05
Fig. 06
A – Type SKINTOP MULTI Version 1 – Maximum number of cables – 22 including 6x8-12 mm; 16x3-7 mm
B – Type SKINTOP MULTI Version 5 with SKINTOP BRUSH ADD-ON 24 for EMC screen contact -
Maximum number of cables – 27 including 27x4-8 mm
C - Type SKINTOP ST-M M20 - GDA Sensor Cable
Note:
1. To ensure an optimum strain relief, the cable bundle can be fixed with help of a cable tie
2. After removing unused cable from SKINTOP MULTI - elastic gel will NOT SEAL, please use silicone to ensure proper
IP (Ingress Protection)
3. Use plug for M20 gas detector gland if gas detector is not present.
NB:
DIFFERENT POTENTIALS 24 V AND 230 V SHOULD BE PLACED IN SEPARATE CABLE ENTRY
C
BBA A