Installation Guide

Installation guide
Pre-programmed Controller MCX15B2 for IPS 8
Replacement of MCX controller
148R9658
148R9658
AN420522619085en-000101 | 1
089
Info for UK customers only : Danfoss Ltd., 22 Wycombe End, HP9 1NB, GB
Імпортер:ТОВ з іі “Данфосс ТОВ” 04080, Київ 80, п/с 168, Україна
© Danfoss | Climate Solutions | 2022.09
Prior to disconnect and remove the old MCX controller it is important to depressurize the ammonia side of the purger unit
by following these steps (see g. 1)
1. Close all supply lines from the purge points of the ammonia system (a)
2. Restart the controller to force pump-down
3. Wait for 20 minutes
4. Stop the compressor and other connected devices by switching OFF:
IPS variants:
084H5001, IPS 8, CE, 230 V AC, 1ph, 50 Hz
084H5002, IPS 8, 230 V AC, 1ph, 60 Hz
4a) Operate QM1: Thermal magnetic miniature circuit breaker - See Fig. 2a
084H5003, IPS 8, UL 230 V AC, 1ph, 60 Hz
4b) Operate Thermal magnetic miniature circuit breakers - See Fig. 2b
11QF1
11QF2
11QF3
12QF4
5. Close the SVA shut-o valve in the drain line (located under the IPS8 (b))
6. Release the remaining system pressure to ambient pressure by opening the SNV drain valve (c). This can also be done by
attaching a permanent magnet on the built-in Main Purge valve (YV1 - AKVA 10) valve, for forced opening.
Exchange of MCX15B2 controller
Switch OFF:
IPS variants:
084H5001, IPS 8, CE, 230 V AC, 1ph, 50 Hz
084H5002, IPS 8, 230 V AC, 1ph, 60 Hz
6a) Operate Thermal magnetic miniature circuit breaker - See Fig. 2a
QM2
QM3
QM4
084H5003, IPS 8, UL 230 V AC, 1ph, 60 Hz
6b) Operate Thermal magnetic miniature circuit breakers - See Fig. 2b
14QF5
14QF6
14QF9
6c) Release MCX15B2 controller. See Fig. 3
6d) Unplug all connectors upper level. See Fig. 3
6e) Unplug all connectors lower level. See Fig. 4
6f) Remove old MCX15B2 and install new MCX15B2 and replug all connectors again on both upper and lower level.
Setting of new MCX15B2 controller
IPS variants:
084H5001, IPS 8, CE, 230 V AC, 1ph, 50 Hz
084H5002, IPS 8, 230 V AC, 1ph, 60 Hz
Operate Thermal magnetic miniature circuit breaker - See Fig. 2a
QM4 - Power to MCX15B2 controller
084H5003, IPS 8, UL 230 V AC, 1ph, 60Hz
Operate Thermal magnetic miniature circuit breakers - See Fig. 2b
14QF9 - Power to MCX15B2 controller
1) Enter password 200 (Main screen\Start\Login\ and enter password).
2) Enter number of Purge point in question for the particular application (Main screen\Parameters\Unit cong\Valve settings\ and
enter the valve in Parameter V10, Max_PP).
3) See general IPS User Guide/Start Up instruction. The pre-programmed MCX15B2 (code number 084H5067) is plug & play ready,
and only where customer specic settings are applicable, these values must additional be entered into MCX15B2.
Switch ON again remaining Thermal magnetic miniature circuit breakers
IPS variants:
084H5001, IPS 8, CE, 230 V AC, 1ph, 50 Hz
084H5002, IPS 8, 230 V AC, 1ph, 60 Hz
QM1
QM2
QM3
084H5003, IPS 8, UL 230 V AC, 1ph, 60 Hz
11Q F1
11Q F2
11Q F3
12QF4
14QF5
14QF6