Installation Guide

Installation guide
Check valve
Type OFC
© Danfoss | Climate Solutions | 2021.12 AN391972458172en-000101 | 1
Refrigerant:
For a complete list of approved refrigerants, visit http://store.danfoss.com/ and search for individual code
numbers, where refrigerants are listed as part of product details.
Oil: OFC valve is designed for an oil-free environment
Interface Connections:
Install valve directly on Danfoss Turbocor compressor, picture shown with vertical down installation.
All fasteners and bolts require stainless steel. Bolts with minimum class A2-70.
Media Temperature:
Min. 0
C / 32 F
Max. 90
C / 19
4
F, short term up to 100 C / 212 F
Contents of accessory box
Outlet flange for 3 1/8 in. copper tube
Outlet flange fasteners
O-ring for outlet flange
O-ring lubrication (2 gram)
Additional check valve springs (2 pcs):
- Yellow spring, for 45
down orientation
- Red spring, for horizontal orientation
Max. Working Pressure:
PS/MWP = 23 bar / 334 psig
020R5432
020R54
32
NOTE: refer to check valve orientation options
below
Torque: 38 Nm ± 4 Nm
Info for UK customers only: Danfoss Ltd., 22 Wycombe End, HP9 1NB, GB
NOTE: Protection of entire valve including steel
nge is recommended after installation for out-
door use.