Installation guide

3.4.2 Foundation for outdoor unit
1. Position the outdoor unit on a stable base that can take the total weight, see Technical data.
2. Secure all four mounting points on a stable base, for example a cast foundation.
100 mm
~900 mm
b
c
a
7
5
4
3
6
1
8
2
Measurements 6-12 kW
1 470 mm
2 480 mm
3 672 mm
4 190 mm
5 65 mm
6 ~1,200 mm
7 ~720 mm
8 Ø 65 mm
Position Description
a Drainage hole
b Foundation
c Gravel
Bolt size
6-12 kW
M12 (4x)
A driptray is installed with the purpose of gathering and draining away melt water during defrosting. Connect
a hose or pipe along with a heat trace cable between the outlet of the drip tray and a drain or a free draining
piece of ground. The heat cable must be connected to the terminal provided and is necessary to prevent ice
blockage.
Check with a spirit level that the outdoor unit is installed horizontally.
VMGFQ202 Danfoss Heating Solutions
14
Installation Guide Domestic heat pumps