Datasheet

The Basic and Basic+ gas detection units are used
for monitoring and warning of hazardous gas
concentrations. They can be used for detecting
commonly used refrigerants. Depending on
the application, they are available with an
electrochemical or a semiconductor sensor.
The Basic and Basic+ gas detection units are
intended to be connected to a central system like
Gas Detection Controller Unit, or a PLC, by either
Analog or RS485 open Modbus communications.
The central system converts the alarm signal from
the Basic unit to activation of alarm devices.
The gas detection units come with a factory
default, 2-step alarm set-up ready for use. The
integrated software enables the user to congure
two individual alarm ranges. Alarm 1, a pre-alarm
indicating the gas level has passed a predened
treshold 1, and - if the gas level passes predened
treshold 2 - the nal alarm 2.
Features Digital, factory congured and pre-calibrated
gas detectors for plug-and-play installation (no
adjustment required)
Easy conguration via intuitive user-interface;
helps simplify operator handling and minimize
risk of operational, settings and calibration
errors
Flexible connection - by either Analog or RS485
open Modbus communications
Fieldbus wiring - connect and power up
to 96 sensors, wire length max. 900 meter
per segment; expansion modules permits
additional segments
Automatic self-diagnostics to ensure correct
communication and operation
Sensor seal cap to prevent premature exposure
during installation
Digital user interface ensures higher sensor
accuracy
Reduced risk of false alarms due to
temperature compensated sensors
Password protected alarm settings allowing
authorized access only
LED status signals and alarms
Buzzer & Light option for local audio and visual
alarms (Basic+)
On-board acknowledge button to reset alarms
and to verify the that no gas leaks are present
Service alerts on unit, controller or both,
readable via service tool Display
Quick and precise calibration procedures -
either by Plug & Play replacement sensors or
calibration with gas. No potentiometers or
multi-meters required
For improved safety and to optimize the
lifetime of the sensor, degenerated sensors
with too low sensitivity (<30%) are rejected
during calibration process.
Conformity to EN 50271, EN 61010-1, ANSI/UL
61010 1, CAN/CSA-C22.2 No. 61010-1
Enables regulatory compliance with EN
378:2016, ISO 5149:2014, IIAR 2-2017, and
ASHRAE 15:2016