User guide

Application Guide | Gas detection in refrigeration systems
© Danfoss | DCS (MWA) | 2018.05 DKRCI.PA.S00.A1.02 | 520H12772 11
Installation guideline When it comes to installation of gas detection
there are two approaches:
Perimeter detection
Point detection
With perimeter detection, you place sensors all
around the perimeter of the space in question, to
make sure you monitor the whole space.
With point detection, you locate a sensor at a
particular position, where you are concerned
about a leak (e.g. at the compressor).
For gases heavier than air, sensors should be
located close to the ground/lowest point.
For gases lighter than air, sensors should be
mounted high up on the walls, ceiling or near
exhaust, but convenient for maintenance.
If the density is equal to air, the sensors should be
mounted at face level.
In some countries it may be mandatory to
have an UPS (Uninterruptible Power Supply)
connected to the gas detectors to ensure safe
operation during a power failure.
Fig. 8: Relative density refrigerant/air
Relative density
(refrigerant/air)
0
1
2
3
4