Specifications
8.1.4 Mains Supply 3 x 525-600VAC
Frequency converter P2K2 P3K0 P5K5 P7K5 P11K P15K P22K P30K P45K P55K P75K P90K
Typical shaft output (kW) 2.2 3.0 5.5 7.5 11.0 15.0 22.0 30.0 45.0 55.0 75.0 90.0
Typical shaft output (hp) 3.0 4.0 7.5 10.0 15.0 20.0 30.0 40.0 60.0 70.0 100.0 125.0
IP frame Ip20 Ip20 Ip20 Ip20 Ip20 Ip20 Ip20 Ip20 Ip20 Ip20 Ip20 Ip20
Max. cable size in terminals (mains, motor) [mm
2
/
AWG]
4/10 4/10 4/10 4/10 10/8 10/8 35/2 35/2 50/1 50/1 95/0 120/
(4/0)
Output current
RELAY 2
130BB632.10
40°C ambient temperature
Continuous
(3x525-550V)[A]
4.1 5.2 9.5 11.5 19.0 23.0 36.0 43.0 65.0 87.0 105.0 137.0
Intermittent
(3x525-550V)[A]
4.5 5.7 10.5 12.7 20.9 25.3 39.6 47.3 71.5 95.7 115.5 150.7
Continuous
(3x551-600V)[A]
3.9 4.9 9.0 11.0 18.0 22.0 34.0 41.0 62.0 83.0 100.0 131.0
Intermittent
(3x551-600V)[A]
4.3 5.4 9.9 12.1 19.8 24.2 37.4 45.1 68.2 91.3 110.0 144.1
Max. input current
RELAY 2
130BB633.10
Continuous
(3x525-550V)[A]
3.7 5.1 8.7 11.9 16.5 22.5 33.1 45.1 66.5 81.3 109.0 130.9
Intermittent
(3x525-550V)[A]
4.1 5.6 9.6 13.1 18.2 24.8 36.4 49.6 73.1 89.4 119.9 143.9
Continuous
(3x551-600V)[A]
3.5 4.8 8.3 11.4 15.7 21.4 31.5 42.9 63.3 77.4 103.8 124.5
Intermittent
(3x551-600V)[A]
3.9 5.3 9.2 12.5 17.3 23.6 34.6 47.2 69.6 85.1 114.2 137.0
Max. mains fuses
Estimated power loss [W], Best case/typical
1)
8.4 112.0 178.0 239.0 360.0 503.0 607.0 820.0 972.0 1182.
0
1281.
0
1437.
0
Weight enclosure IP54kg] 6.6 6.6 6.6 6.6 11.5 11.5 24.5 24.5 36.0 36.0 51.0 51.0
Efficiency [%], Best case/Typical 1 97.0 97.0 97.0 97.0 97.0 97.0 97.5 97.5 98.0 98.0 98.4 98.5
Output current
50°C ambient temperature
Continuous
(3x525-550V)[A]
2.9 3.6 6.7 8.1 13.3 16.1 25.2 30.1 45.5 60.9 73.5 95.9
Intermittent
(3x525-550V)[A]
3.2 4.0 7.4 8.9 14.6 17.7 27.7 33.1 50.0 67.0 80.9 105.5
Continuous
(3x551-600V)[A]
2.7 3.4 6.3 7.7 12.6 15.4 23.8 28.7 43.3 58.1 70.0 91.7
Intermittent
(3x551-600V)[A]
3.0 3.7 6.9 8.5 13.9 16.9 26.2 31.6 47.7 63.9 77.0 100.9
General Specifications and ... VLT HVAC Basic Drive Design Guide
MG.18.C2.02 - VLT
®
is a registered Danfoss trademark 85
8 8