Specifications
8.1.2 Mains Supply 3 x 380-480VAC
Frequency converter PK37 PK75 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K
Typical shaft output (kW) 0.37 0.75 1.5 2.2 3.0 4.0 5.5 7.5 11.0 15.0 18.0 22.0 30.0 37.0 45.0 55.0 75.0 90.0
Typical shaft output (hp) 0.5 1.0 2.0 3.0 4.0 5.0 7.5 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0 70.0 100.0 125.0
IP20 frame H1 H1 H1 H2 H2 H2 H3 H3 H4 H4 H5 H5 H6 H6 H6 H7 H7 H8
Max. cable size in terminals (mains, motor)
[mm
2
/AWG]
4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10 16/6 16/6 16/6 16/6 35/2 35/2 35/2 50/1 95/0 120/25
0MCM
Output current
RELAY 2
130BB632.10
40°C ambient temperature
Continuous
(3x380-440V)[A]
1.2 2.2 3.7 5.3 7.2 9.1 12.0 15.5 23.0 31.0 37.0 42.5 61.0 73.0 90.0 106.0 147.0 177.0
Intermittent
(3x380-440V)[A]
1.3 2.4 4.1 5.8 7.9 9.9 13.2 17.1 25.3 34.0 40.7 46.8 67.1 80.3 99.0 116.0 161.0 194.0
Continuous
(3x440-480V)[A]
1.1 2.1 3.4 4.8 6.3 8.2 11.0 14.0 21.0 27.0 34.0 40.0 52.0 65.0 80.0 105.0 130.0 160.0
Intermittent
(3x440-480V)[A]
1.2 2.3 3.7 5.3 6.9 9.0 12.1 15.4 23.1 29.7 37.4 44.0 57.2 71.5 88.0 115.0 143.0 176.0
Max. input current
RELAY 2
130BB633.10
Continuous
(3x380-440V)[A]
1.2 2.1 3.5 4.7 6.3 8.3 11.2 15.1 22.1 29.2 35.2 41.5 57.0 70.0 84.0 103.0 140.0 166.0
Intermittent
(3x380-440V)[A]
1.3 2.3 3.9 5.2 6.9 9.1 12.3 16.6 24.3 32.9 38.7 45.7 62.7 77.0 92.4 113.0 154.0 182.0
Continuous
(3x440-480V)[A]
1.0 1.8 2.9 3.9 5.3 6.8 9.4 12.6 18.4 24.7 29.3 34.6 49.2 60.6 72.5 88.6 120.9 142.7
Intermittent
(3x440-480V)[A]
1.1 2.0 3.2 4.3 5.8 7.5 10.3 13.9 20.2 27.2 32.2 38.1 54.1 66.7 79.8 97.5 132.9 157.0
Max. mains fuses See 5.1.4 Fuses
General Specifications and ... VLT HVAC Basic Drive Design Guide
82 MG.18.C2.02 - VLT
®
is a registered Danfoss trademark