Specifications
8 General Specifications and Troubleshooting
8.1 Mains Supply Tables
8.1.1 Mains Supply 3 x 200-240V AC
Frequency converter PK2
5
PK3
7
PK7
5
P1K
5
P2K2 P3K
7
P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K
Typical shaft output (kW) 0.25 0.37 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15.0 18.5 22.0 30.0 37.0 45.0
Typical shaft output (hp) 0.33 0.5 1.0 2.0 3.0 5.0 7.5 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0
IP20 frame H1 H1 H1 H1 H2 H3 H4 H4 H5 H6 H6 H7 H7 H8 H8
Max. cable size in terminals (mains,
motor) [mm
2
/AWG]
4/10 4/10 4/10 4/10 4/10 4/10 16/6 16/6 16/6 35/2 35/2 50/1 50/1 95/0 120/
(4/0)
Output current
RELAY 2
130BB632.10
40°C ambient temperature
Continuous
(3x200-240V) [A]
1.5 2.2 4.2 6.8 9.6 15.2 22.0 28.0 42.0 59.4 74.8 88.0 115.0 143.0 170.0
Intermittent
(3x200-240V)[A]
1.7 2.4 4.6 7.5 10.6 16.7 24.2 30.8 46.2 65.3 82.3 96.8 126.5 157.3 187.0
Max. input current
RELAY 2
130BB633.10
Continuous
(3x200-240V) [A]
1.1 1.6 2.8 5.6 8.8/7
.2
14.1
/
12.0
21.0/
18.0
28.3/
24.0
41.0/
38.2
52.7 65.0 76.0 103.7 127.9 153.0
Intermittent
(3x200-240V)[A]
1.2 1.8 3.1 6.2 9.5/7
.9
15.5
/
13.2
23.1/
19.8
31.1/
26.4
45.1/
42.0
58.0 71.5 83.7 114.1 140.7 168.3
Max. mains fuses
See 5.1.4 Fuses
Estimated power
loss [W], Best
case/typical
1)
12/1
4
15/1
8
21/2
6
48/6
0
80/1
02
97/1
20
182/
204
229/
268
369/
386
512 658 804 1015 1459 1350
Weight enclosure
IP20 [kg]
2. 2.0 2.0 2.1 3.4 4.5 7.9 7.9 9.5 24.5 24.5 36.0 36.0 51.0 51.0
Efficiency [%],
Best case/Typical
1
97.0
/
96.5
97.3
/
96.8
98.0/
97.6
97.6
/
97.0
97.1/
96.3
97.9
/
97.4
97.3/
97.0
98.5/
97.1
97.2/
97.1
97.0 96.9 96.8 97.0 96.5 97.3
Output current
50°C ambient temperature
Continuous
(3x200-240V) [A]
1.5 1.9 3.5 6.8 9.6 13.0 19.8 23.0 33.0 53.5 66.6 79.2 103.5 128.7 153.0
Intermittent
(3x200-240V) [A]
1.7 2.1 3.9 7.5 10.6 14.3 21.8 25.3 36.3 58.9 73.3 87.1 113.9 141.6 168.3