Specifications

7.9.5 Conversion Factor
The different attributes for each parameter can be seen in
the section on factory settings. Since a parameter value
can only be transferred as a whole number, a conversion
factor must be used to transfer decimals. Please refer to
the Parameters section.
7.9.6 Parameter Values
Standard Data Types
Standard data types are int16, int32, uint8, uint16 and
uint32. They are stored as 4x registers (40001 4FFFF). The
parameters are read using function 03HEX "Read Holding
Registers." Parameters are written using the function 6HEX
"Preset Single Register" for 1 register (16 bits), and the
function 10HEX "Preset Multiple Registers" for 2 registers
(32 bits). Readable sizes range from 1 register (16 bits) up
to 10 registers (20 characters).
Non standard Data Types
Non standard data types are text strings and are stored as
4x registers (40001 4FFFF). The parameters are read
using function 03HEX "Read Holding Registers" and written
using function 10HEX "Preset Multiple Registers." Readable
sizes range from 1 register (2 characters) up to 10 registers
(20 characters).
7.10
Examples
The following examples illustrate various Modbus RTU
commands. If an error occurs, please refer to the Exception
Codes section.
7.10.1
Read Coil Status (01 HEX)
Description
This function reads the ON/OFF status of discrete outputs
(coils) in the frequency converter. Broadcast is never
supported for reads.
Query
The query message specifies the starting coil and quantity
of coils to be read. Coil addresses start at zero, i.e. coil 33
is addressed as 32.
Example of a request to read coils 33-48 (Status Word)
from slave device 01.
Field Name
Example (HEX)
Slave Address 01 (frequency converter address)
Function 01 (read coils)
Starting Address HI 00
Starting Address LO 20 (32 decimals) Coil 33
No. of Points HI 00
No. of Points LO 10 (16 decimals)
Error Check (CRC) -
Response
The coil status in the response message is packed as one
coil per bit of the data field. Status is indicated as: 1 = ON;
0 = OFF. The LSB of the first data byte contains the coil
addressed in the query. The other coils follow toward the
high order end of this byte, and from ‘low order to high
order’ in subsequent bytes.
If the returned coil quantity is not a multiple of eight, the
remaining bits in the final data byte will be padded with
zeros (toward the high order end of the byte). The Byte
Count field specifies the number of complete bytes of
data.
Field Name Example (HEX)
Slave Address 01 (frequency converter address)
Function 01 (read coils)
Byte Count 02 (2 bytes of data)
Data (Coils 40-33) 07
Data (Coils 48-41) 06 (STW=0607hex)
Error Check (CRC) -
NOTE
Coils and registers are addressed explicit with an off-set of
-1 in Modbus.
I.e. Coil 33 is addressed as Coil 32.
7.10.2 Force/Write Single Coil (05 HEX)
Description
This function forces a writes a coil to either ON or OFF.
When broadcast the function forces the same coil
references in all attached slaves.
Query
The query message specifies the coil 65 (parameter write
control) to be forced. Coil addresses start at zero, i.e. coil
65 is addressed as 64. Force Data = 00 00HEX (OFF) or FF
00HEX (ON).
Field Name
Example (HEX)
Slave Address 01 (frequency converter address)
Function 05 (write single coil)
Coil Address HI 00
Coil Address LO 40 (64 decimal) Coil 65
Force Data HI FF
Force Data LO 00 (FF 00 = ON)
Error Check (CRC) -
RS-485 Installation and Set... VLT HVAC Basic Drive Design Guide
MG.18.C2.02 - VLT
®
is a registered Danfoss trademark 75
7 7