Specifications
Motor Set-up
The Quick Menu Motor Set-up guides through the needed
motor parameters.
No & Name Range Default Function
0-03 Regional
Settings
[0] Interna-
tional
[1] US
0
1-20 Motor
Powerr
0.12-110kW/
0.16-150hp
Size related Enter motor
power from
nameplate data
1-22 Motor
Voltage
50.0 - 1000.0V Size related Enter motor
voltage from
nameplate data
1-23 Motor
Frequency
20.0 - 400.0Hz Size related Enter motor
frequency from
nameplate data
1-24 Motor
Current
0.01 -
10000.00A
Size related Enter motor
current from
nameplate data
1-25 Motor
Nominal
Speed
100.0 - 9999.0
RPM
Size related Enter motor
nominal speed
from nameplate
data
4-12 Motor
Speed Low
Limit [Hz]
0.0 - 400Hz 0.0Hz Enter the
minimum limit
for low speed
4-14 Motor
Speed High
Limit [Hz]
0.0 - 400HZ 65 Enter the
maximum limit
for high speed
3-41 Ramp 1
Ramp up Time
0.05 - 3600.0 s Size related Ramp up time
from 0 to rated
1-23 Motor
Frequency
3-42 Ramp 1
Ramp Down
Time
0.05 - 3600.0 s Size related Ramp down time
from rated
1-23 Motor
Frequency to 0
1-73 Flying
Start
[0] Disabled
[1] Enabled
0 Select Enable to
enable the
frequency
converter to
catch a spinning
motor
Changes Made
Changes Made lists all parameters changed since factory
setting. Only the changed parameters in current edit-setup
are listed in changes made.
If the parameter's value is changed back to factory
setting's value from another different value, the parameter
will NOT be listed in Changes Made.
1. Press [MENU] key to enter the Quick Menu until
indicator in display is placed above Quick Menu.
2.
Press [
▲
] [
▼
] to select either FC 101 wizard,
closed loop setup, motor setup or changes made,
then press [OK].
3.
Press [
▲
] [
▼
] to browse through the parameters
in the Quick Menu.
4. Press [OK] to select a parameter.
5.
Press [
▲
] [
▼
] to change the value of a parameter
setting.
6. Press [OK] to accept the change.
7. Press either [Back] twice to enter “Status”, or
press [Menu] once to enter “Main Menu”.
6.3.4
Main Menu
[Main Menu] is used for programming all parameters. The
Main Menu parameters can be accessed immediately
unless a password has been created via 0-60 Main Menu
Password. For the majority of VLT HVAC Basic Drive
applications it is not necessary to access the Main Menu
parameters but instead the Quick Menu provides the
simplest and quickest access to the typical required
parameters.
The Main Menu accesses all parameters.
1. Press [MENU] key until indicator in display is
placed above “Main Menu”.
2.
Use [
▲
] [
▼
] to browse through the parameter
groups.
3. Press [OK] to select a parameter group.
4.
Use [
▲
] [
▼
] to browse through the parameters in
the specific group.
5. Press [OK] to select the parameter.
6.
Use [
▲
] [
▼
] to set/change the parameter value.
[BACK] is used to go one level back.
How to Programme VLT HVAC Basic Drive Design Guide