Specifications
5.2.2 Electrical Installation in General
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper
conductors required, (75°C) recommended.
Power (kW) Torque (Nm)
Frame IP class 3 x 200-240V 3 x 380-480 Line Motor DC
connection
Control
terminals
Earth Relay
H1 IP20 0.25-1.5 0.37-1.5 1.4 0.8 0.8 0.5 3 0.5
H2 IP20 2.2 2.2-4 1.4 0.8 0.8 0.5 3 0.5
H3 IP20 3.7 5.5-7.5 1.4 0.8 0.8 0.5 3 0.5
H4 IP20 5.5-7.5 11-15 1.2 1.2 1.2 0.5 3 0.5
H5 IP20 11 18.5-22 1.2 1.2 1.2 0.5 3 0.5
H6 IP20 15-18 30-45 4.5 4.5 - 0.5 3 0.5
H7 IP20 22-30 55 10 10 - 0.5 3 0.5
H7 IP20 - 75 14 14 - 0.5 3 0.5
H8 IP20 37-45 90
24
2
24
2
- 0.5 3 0.5
Power (kW) Torque (Nm)
Frame IP class 3 x 380-480 Line Motor DC connection Control
terminals
Earth Relay
I6 IP54 22-37 4.5 4.5 - 0.5 3 0.6
I7 IP54 45-55 10 10 - 0.5 3 0.6
I8 IP54 75-90
14/24
1
14/24
1
- 0.5 3 0.6
Power (kW) Torque (Nm)
Frame IP class 3 x 525-600 Line Motor DC connection Control
terminals
Earth Relay
H9 IP20 2.2-7.5 1.8 1.8 not
recommended
0.5 3 0.6
H10 IP20 11-15 1.8 1.8 not
recommended
0.5 3 0.6
H6 IP20 22-30 4.5 4.5 - 0.5 3 0.5
H7 IP20 45-55 10 10 - 0.5 3 0.5
H8 IP20 75-90
14/24
1
14/24
1
- 0.5 3 0.5
Table 5.2 Details of Tightening Torques
1
Cable dimensions
≤
95mm
2
2
Cable dimensions > 95mm
2
How to Install VLT HVAC Basic Drive Design Guide
48 MG.18.C2.02 - VLT
®