Operating instructions

9.4.2 Input variables (nvi)
Variable Function Variable Name SNVT type Profile FC 100 par.
Start/Stop nviStartStop SNVT_switch FC VSD CTW/reference
Control word nviControlword SNVT_state FC VSD CTW
Reset fault nviResetFaut SNVT_switch FC VSD CTW
Reference [%] nviRefPcnt SNVT_lev_percent FC VSD Reference
Reference [Hz] nviRefHz SNVT_freq_hz FC VSD Reference
CL Setpoint 1 nviSetpoint1 SNVT_lev_percent FC VSD 20-21
CL Setpoint 2 nviSetpoint2 SNVT_lev_percent FC VSD 20-22
CL Setpoint 3 nviSetpoint3 SNVT_lev_percent FC VSD 20-23
Bus feedback 1 nviFeedback1 SNVT_lev_percent FC VSD 8-94
Bus feedback 2 nviFeedback2 SNVT_lev_percent FC VSD 8-95
Bus feedback 3 nviFeedback3 SNVT_lev_percent FC VSD 8-96
Digital/relay outputs nviDigiOutput SNVT_state_64 FC VSD 5-90
Analog output (42) nviAnOut1 SNVT_lev_percent FC VSD 6-53
Analog output (X30/8) nvi101AnOut1 SNVT_lev_percent FC VSD 6-63
Analog output (X42/7) nvi109AnOut1 SNVT_lev_percent FC VSD 26-43
Analog output (X42/9) nvi109AnOut2 SNVT_lev_percent FC VSD 26-53
Analog output (X42/11) nvi109AnOut3 SNVT_lev_percent FC VSD 26-63
Setting of RTC nviTimeStamp SNVT_time_stamp FC VSD 0-70
ECB option Mode nviECBMode SNVT_state FC VSD 31-00
ECB By-pass activation nviECBActivation SNVT_switch FC VSD 31-19
Parameter access command nviParamRequest UNVT_param_request FC VSD -
Drive speed setpoint nviDrvSpeedStpt SNVT_switch VSD 6010 CTW / Reference
Standard Node Object nviRequest SNVT_obj_request Node obj. -
9.4.3 Configuration properties (nci)
Variable function Variable name SNVT type Profile
FC 100
parameter
Max. motor speed [%] nciMaxSpeed SNVT_lev_percent VSD 6010 4-13
Min. motor speed [%] nciMinSpeed SNVT_lev_percent VSD 6010 4-11
Nom. motor speed [RPM] nciNmlSpeed SNVT_rpm VSD 6010 1-25
Nom. motor frequency [Hz] nciNmlFreq SNVT_freq_hz VSD 6010 1-23
Min. ramp-up time [s] nciRampUpTime SNVT_time_sec VSD 6010 3-41
Min. ramp-down time [s] nciRampDownTime SNVT_time_sec VSD 6010 3-42
Heartbeat time [s] nciSndHrtBt SNVT_time_sec VSD 6010 -
Max Send Time (Heartbeat) nciMaxStsSendT SNVT_elapsed_tm Node obj. -
Min Send Time (Inhibit timer) nciMinSendT SNVT_elapsed_tm Virtual obj. -
VLT® FC 100 LonWorks 9 Troubleshooting
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
63