Operating instructions

NB!
This parameter is active only when par.8-01
Control Site
is set to [0]
Digital and control word
.
8-55 Set-up Select
Option: Function:
Select control of the frequency converter set-up selection via the terminals (digital input) and/or via
the fieldbus.
[0] Digital input Activates the set-up selection via a digital input.
[1] Bus Activates the set-up selection via the serial communication port or fieldbus option.
[2] Logic AND Activates the set-up selection via the fieldbus/serial communication port, AND additionally via one
of the digital inputs.
[3] * Logic OR Activate the set-up selection via the fieldbus/serial communication port OR via one of the digital
inputs.
NB!
This parameter is active only when par.8-01
Control Site
is set to [0]
Digital and control word
.
8-56 Preset Reference Select
Option: Function:
Select control of the frequency converter Preset Reference selection via the terminals (digital input)
and/or via the fieldbus.
[0] Digital input Activates Preset Reference selection via a digital input.
[1] Bus Activates Preset Reference selection via the serial communication port or fieldbus option.
[2] Logic AND Activates Preset Reference selection via the fieldbus/serial communication port, AND additionally
via one of the digital inputs.
[3] * Logic OR Activates the Preset Reference selection via the fieldbus/serial communication port OR via one of
the digital inputs.
NB!
This parameter is active only when par.8-01
Control Site
is set to [0]
Digital and control word
.
VLT® FC 100 LonWorks 8 Parameters
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
53