Operating instructions

[2] USB Port
[3] * Option A
[4] Option B
[5] Option C0
[6] Option C1
NB!
This parameter cannot be adjusted while the motor is running.
8-03 Control Timeout Time
Range: Function:
60.0 s* [1.0 - 18000.0 s] Enter the maximum time expected to pass between the reception of two consecutive telegrams. If
this time is exceeded, it indicates that the serial communication has stopped. The function selected
in par.8-04
Control Timeout Function
Control Time-out Function
will then be carried out.
In LonWorks the following variables will trigger the Control Word Time parameter:
nviStartStop
nviReset Fault
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
8-04 Control Timeout Function
Option: Function:
Select the time-out function. The time-out function is activated when the control word fails to be
updated within the time period specified in par.8-03
Control Timeout Time
. Choice [20] only appears
after setting the N2 protocol.
[0] * Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max. speed
[5] Stop and trip
[7] Select setup 1
[8] Select setup 2
[9] Select setup 3
[10] Select setup 4
[20] N2 Override Release
In LonWorks, the time-out function is also activated when the following SNVT's fail to be updated within the time period specified in par.8-03
Control
Timeout Time
:
nviStartStop
nviReset Fault
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
8 Parameters VLT® FC 100 LonWorks
50
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
8