Operating instructions
5.7 Node Object
5.7.1 Node Object
These variables are used for controlling all functional blocks via the com-
missioning tool.
5.7.2 Object Request
Variable name: SNVT type: Supported functions: Description:
nviRequest SNVT_obj_request RQ_Normal Returns the specified functional block to normal operation.
RQ_Update_Status Requests the status of the specified functional block.
RQ_Report_Mask
Requests a status mask reporting the status bits that are supported
by the specified functional block.
RQ_Disabled
Requests the specified functional block to change to the disabled
state. In the disabled state, output network variables belonging to
the functional block are not propagated within the network.
RQ_Enable
Requests the specified functional block to change to the enabled
state. In the enabled state, output network variables belonging to
the functional block are propagated within the network as defined
by the functional block.
5.7.3 Object Response
Variable name: SNVT type: Description:
nvoStatus SNVT_object_status
This output network variable reports the status for any functional block on a device. It is also used to report
the status of the entire device and all functional blocks on the device.
5.7.4 Max. Send Time (Heartbeat)
Variable
name:
SNVT
type:
Default value: Min value: Max value:
nciMaxStsSendT SNVT_elapsed_tm 00:0:0:0 00:0:0:0 017:59:59:999
This variable configures a timer to send the nvoStatus object but only if bound to an input variable.
Maximum is '0 17:59:59:999' (0 days, 17 hours, 59 minutes, 59 seconds and 999 milliseconds).
Setting the timer to '0 0:0:0:0' disables it.
Network timer functions monitor node presence and control behaviour in the event of network problems occurring.
VLT® FC 100 LonWorks 5 Configuration of the system
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
39