Operating instructions
5.6.5 Min Ramp-up Time [s]
Variable
name:
SNVT
type:
Default value: Min value: Max value:
nciRampUpTime SNVT_time_sec 10 s 1 s 3,600 s
This variable configures the Ramp 1 ramp-up time and associates it with par. 3-41
Ramp 1 Ramp Up Time
.
5.6.6 Min Ramp-down Time [s]
Variable
name:
SNVT
type:
Default value: Min value: Max value:
nciRampDownTime SNVT_time_sec 10 s 1 s 3,600 s
This variable configures the Ramp 1 ramp-down time and compares it with par. 3-42
Ramp 1 Ramp Down Time
.
5.6.7 Heartbeat Time [s]
Variable
name:
SNVT
type:
Default value: Min value: Max value:
nciSndHrtBt SNVT_time_sec 0 s 0 s 6,553.4 s
This variable configures a heartbeat timer to send the following variables:
nvoDrvCurnt
nvoDrvSpeed
nvoDrvVolt
nvoDrvPwr
Setting the timer to 0.0 disables the timer.
Heartbeat timers have the purpose of sending out heartbeat signals containing specific data, enabling management systems to prove that the node is
present on the network and working correctly. Only bound variables will be transmitted.
5 Configuration of the system VLT® FC 100 LonWorks
38
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
5