Operating instructions
5.6 Network Variable Description - VSD Profile - Configuration
5.6.1 Max Motor Speed [%]
Variable
name:
SNVT
type:
Default value: Min value: Max value:
nciMaxSpeed SNVT_lev_percent 100 % 0 % 163.830 %
This variable configures the maximum motor speed in % and associates it with par. 4-13
Motor Speed High Limit [RPM]
(par. 4-14 in Hz mode).
The value is entered as a percent of nominal speed, as defined by the Nominal Speed (nciNmlSpeed) configuration value.
For more information on reference scaling, please refer to the
How to Control the FC 100
section. If a value higher than 163.830% is requested, use the
parameter access command.
5.6.2 Min Motor Speed [%]
Variable
name:
SNVT
type:
Default value: Min value: Max value:
nciMinSpeed SNVT_lev_percent 0 % 0 % 163.830 %
This variable configures the minimum motor speed in % and associates it with par. 4-11
Motor Speed Low Limit [RPM]
(par. 4-12 in Hz mode).
The value is entered as a percent of nominal speed, as defined by the Nominal Speed (nciNmlSpeed) configuration value.
For more information on reference scaling, please refer to the
How to Control the FC 100
section.
5.6.3 Nom Motor Speed [RPM]
Variable
name:
SNVT
type:
Default value: Min value: Max value:
nciNmlSpeed SNVT_rpm 1420 RPM 10 RPM 65,534 RPM
This variable configures the nominal motor speed in RPM and associates it with par. 1-25
Motor Nominal Speed
.
NB!
Please note that this variable can be adjusted only while the frequency converter is stopped.
If a value lower than 10 RPM is entered, nciNmlSpeed will be set to 10 RPM.
5.6.4 Nominal Motor Frequency [Hz]
Variable
name:
SNVT
type:
Default value: Min value: Max value:
nciNmlFreq SNVT_freq_hz 50 Hz 20 Hz 100 Hz
This variable configures the nominal motor frequency and associates it with par. 1-23
Motor Frequency
.
NB!
Please note that this variable can be adjusted only while the frequency converter is stopped.
If a value lower than 20 Hz is entered, nciNmlFreq will be set to 20 Hz.
VLT® FC 100 LonWorks 5 Configuration of the system
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
37
5