Operating instructions
5.5 Network Variable Description - VSD Profile - Output
5.5.1 Drive Speed
Variable
name:
SNVT
type:
Value:
nvoDrvSpeed SNVT_lev_percent Min: Max: Resolution:
-163.840 % +163.830 % 0.005 %
This variable contains the frequency converter speed as a percentage of the nominal speed.
5.5.2 Output Current
Variable
name:
SNVT
type:
Value:
nvoDrvCurnt SNVT_amp Min: Max: Resolution:
0 A 3,276.6 A 0.1 A
This variable contains the frequency converter output current in ampere measured as a mean value, IRMS.
The value is filtered and therefore approximately 1.3 seconds delayed before a current change is reflected in the output variable.
5.5.3 Output Voltage
Variable
name:
SNVT
type:
Value:
nvoDrvVolt SNVT_volt Min: Max: Resolution:
0 V 3,276.6 V 0.1 V
This variable contains the frequency converter output voltage.
5.5.4 Output Power
Variable
name:
SNVT
type:
Value:
nvoDrvPwr SNVT_power_kilo Min: Max: Resolution:
0 kW 6,554.4 kW 0.1 kW
This variable contains the frequency converter output power in kW, calculated on the basis of the actual motor voltage and current.
The value is filtered and therefore approximately 1.3 seconds delayed before a power change is reflected in the output variable.
5.5.5 Running Hours
Variable
name:
SNVT
type:
Value:
nvoDrvRunHours SNVT_time_hour Min: Max: Resolution:
0 hr 65,534 hr 1 hr
This variable contains the total running hours of the motor.
5 Configuration of the system VLT® FC 100 LonWorks
36
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
5