Operating instructions
5.3.4 Configuration Properties (nci)
Variable function Variable name SNVT type Profile
FC 100 pa-
rameter
Max. motor speed [%] nciMaxSpeed SNVT_lev_percent VSD 6010 4-13
Min. motor speed [%] nciMinSpeed SNVT_lev_percent VSD 6010 4-11
Nom. motor speed [RPM] nciNmlSpeed SNVT_rpm VSD 6010 1-25
Nom. motor frequency [Hz] nciNmlFreq SNVT_freq_hz VSD 6010 1-23
Min. ramp-up time [s] nciRampUpTime SNVT_time_sec VSD 6010 3-41
Min. ramp-down time [s] nciRampDownTime SNVT_time_sec VSD 6010 3-42
Heartbeat time [s] nciSndHrtBt SNVT_time_sec VSD 6010 -
A range of network configuration variables (SCPT's) is available for configuration of the frequency converter parameters. These parameters require setting
only once, usually following installation.
NB!
Please note that the settings written to configuration properties (nci's) will be stored in the non-volatile memory. Continuous writing
to configuration properties may damage the non-volatile memory.
5.4 Network Variable Description - VSD Profile - input
5.4.1 Frequency Converter Speed Setpoint
Variable name: SNVT type: State: Value: Command:
nviDrvSpeedStpt SNVT_switch 0 (False) Any Stop
1 (True) 0 Running 0 %
1 (True) 1-200 Running 0.5 to 100 %
1 (True) 201-255 Running 100 %
0xFF (default) Any AUTO (invalid, no action)
This input variable provides start / stop control and a speed reference.
VLT® FC 100 LonWorks 5 Configuration of the system
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
35