Operating instructions
5.3 VSD 6010 Profile
5.3.1 Introduction
The
Variable Speed Drive 6010
profile is a LonMark standardized functional profile.
It describes how to control a variable speed frequency converter.
For example, an air handling unit controller that sends messages to facilitate control of the start/stop and speed reference of the VSD. The VSD will deliver
messages such as the actual frequency converter speed and output current to the controller, operating interfaces and energy management systems.
5.3.2 Input Variables
Variable function Variable name SNVT type Profile FC 100 parameter
Drive speed setpoint nviDrvSpeedStpt SNVT_switch VSD 6010 CTW / Reference
5.3.3 Output Variables
Variable function Variable name SNVT type Profile FC 100 parameter
Drive speed nvoDrvSpeed SNVT_lev_percent VSD 6010 16-05
Output current nvoDrvCurnt SNVT_amp VSD 6010 16-14
Output voltage nvoDrvVolt SNVT_volt VSD 6010 16-12
Output power nvoDrvPwr SNVT_power_kilo VSD 6010 16-10
Running hours nvoDrvRunHours SNVT_time_hour VSD 6010 15-01
5 Configuration of the system VLT® FC 100 LonWorks
34
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
5