Operating instructions

Analog Input (X42/1)
Variable
name:
SNVT
type:
Value:
nvo109AnIn1 Changeable Min. Max. Resolution:
SNVT_volt 0 V 10 V 0.1 V
SNVT_temp_p -273.15 °C 327.66 °C 0.01 °C
SNVT_lev_percent 0 % 100 % 0,1 %
Analog Input (X42/3)
Variable
name:
SNVT
type:
Value:
nvo109AnIn2 Changeable Min. Max. Resolution:
SNVT_volt 0 V 10 V 0.1 V
SNVT_temp_p -273.15 °C 327.66 °C 0.01 °C
SNVT_lev_percent 0 % 100 % 0,1 %
Analog Input (X42/5)
Variable
name:
SNVT
type:
Value:
nvo109AnIn3 Changeable Min. Max. Resolution:
SNVT_volt 0 V 10 V 0.1 V
SNVT_temp_p -273.15 °C 327.66 °C 0.01 °C
SNVT_lev_percent 0 % 100 % 0,1 %
These variables contain the value allocated to the analog input terminal X42/1-5 of the
Analog I/O option, MCB109
. The variable type is changeable with
the commissioning tool.
NB!
This variable is available only if the Analog I/O option (MCB109) has been installed.
5 Configuration of the system VLT® FC 100 LonWorks
32
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
5