Operating instructions

Alarm Flag
Variable
name:
SNVT
type:
State: Value: Command:
nvoAlarm SNVT_switch 0 (False) 0 No alarm(s) present
1 (True) 100 Alarm(s) present
This variable indicates whether any alarm is present.
Warning Flag
Variable
name:
SNVT
type:
State: Value: Command:
nvoWarning SNVT_switch 0 (False) 0 No warning(s) present
1 (True) 100 Warning(s) present
This variable indicates whether any warning is present.
Alarm Word
Variable
name:
SNVT
type:
State:
nvoAlarmword SNVT_state_64 Boolean 1 bit x 64
This variable contains the complete alarm word.
For more detailed information on the Alarm Word, please refer to the
Troubleshooting
section of this manual.
NB!
Please note that in the representation of the Alarm Word in the LonMaker Browser, the Least Significant Bit (LSB) is to the far left.
Warning Word
Variable
name:
SNVT
type:
State:
nvoWarningword SNVT_state_64 Boolean 1 bit x 64
This variable contains the complete warning word.
For more detailed information on the Warning Word, please refer to the
Troubleshooting
section of this manual.
NB!
Please note that in the representation of the Warning Word in the LonMaker Browser, the Least Significant Bit (LSB) is to the far left.
VLT® FC 100 LonWorks 5 Configuration of the system
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
29