Installation guide
InstallationGuideECLComfort310,applicationA361
6.8Application
Mexercise(valveexercise)
12023
CircuitSettingrange
Factorysetting
2
OFF/ONOFF
Exercisesthevalvetoavoidblockinginperiodswithoutheatdemand.
OFF:
ON:
DHWpriority(closedvalve/normaloperation)
12052
CircuitSettingrange
Factorysetting
2
OFF/ONOFF
Theheatingcircuitcanbeclosedwhenthecontrolleractsasslaveandwhen
DHWchargingisactiveinthemaster.
OFF:
ON:
*Thedesiredowtemperatureissettothevaluesetin
‘Frostpr.T’
PfrostT
12077
CircuitSettingrange
Factorysetting
2
OFF/-10...20°C2°C
Whentheoutdoortemperatureisbelowthesettemperaturein‘PfrostT’,
thecontrollerautomaticallyswitchesONthecirculationpumptoprotect
thesystem.
OFF:
-10...20:
PheatT(heatdemand)
12078
CircuitSettingrange
Factorysetting
2
5...40°C20°C
Whenthedesiredowtemperatureisabovethesettemperaturein‘PheatT’ ,
thecontrollerautomaticallyswitchesONthecirculationpump.
5...40: