Pressure,diff.(switchingdifference)
12322
CircuitSettingrange
Factorysetting
2
0.1...5.0bar1.5bar
Settingoftheswitchingdifferenceformeasuredstaticpressure(pressure
transmitter).Thedifferenceissymmetricalaroundthe'Pressuredes. 'See
also'Pressuredes. '
Pexercise(pumpexercise)
12320
CircuitSettingrange
Factorysetting
2
OFF/1...200sOFF
Thetimethepumpisactivatedduringexercise.Exercisetakesplaceevery
day(at12:00).
OFF:
1...200:
Valvedelay
12325
CircuitSettingrange
Factorysetting
20...30s
1s
SettingofthetimeforactivationoftheON/OFFvalveafterstartoftherell
waterpump.
RellpumpON
OFF
Rellvalve
ON
OFF
Time
‘Valvedelay’
No.ofpumps
12326
CircuitSettingrange
Factorysetting
2
OFF/1...2
1
Settingofthenumberofpumpsintherellwatercircuit.
OFF:
1...2:
ECL485
communication
bus
Rellwater
pump
Rellwater
valve