Installation guide

InstallationGuideECLComfort310,applicationA361
6.5Controlparameters
Motorpr.(motorprotection)
12174
CircuitSettingrange
Factorysetting
2
OFF/10...59mOFF
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting
actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection
increasesthelifetimeofallinvolvedcomponents.
OFF:

10...59:



Xp(proportionalband)
12184
CircuitSettingrange
Factorysetting
2
5...250K40K


Tn(integrationtimeconstant)
12185
CircuitSettingrange
Factorysetting
21...999s20s




Mrun(runningtimeofthemotorizedcontrolvalve)
12186
CircuitSettingrange
Factorysetting
25...250s20s




Howtocalculatetherunningtimeofamotorizedcontrolvalve


Seatedvalves


Example:
5.0mmx15sec./mm=75sec.
Rotatingvalves


Example:90degr.x2sec./degr.=180sec.


