Installation guide

InstallationGuideECLComfort310,applicationA361
Ramp(referenceramping)
12013
CircuitSettingrange
Factorysetting
2
OFF/1...99mOFF
Thetime(minutes)inwhichthedesiredowtemperatureincreases
graduallytoavoidloadpeaksintheheatsupply.
OFF:

1-99m:





Temp.°C
Time(min.)
Rampingtime
Optimizer(optimizingtimeconstant)
12014
CircuitSettingrange
Factorysetting
2
OFF/10...59OFF
Optimizesthestartandstoptimesforthecomforttemperatureperiodto
obtainthebestcomfortatthelowestenergyconsumption.
Thelowertheoutdoortemperature,theearliertheheatingcut-in.Thelower
theoutdoortemperature,thelatertheheatingcut-out.
Theoptimizedheatingcut-outtimecanbeautomaticordisabled.The
calculatedstartandstoptimesarebasedonthesettingoftheoptimizing
timeconstant.



OFF:


10...59:


LeftdigitHeataccumulationofthe
building
Systemtype















Rightdigit
DimensioningtemperatureCapacity











Dimensioningtemperature:



Example









