Installation guide
InstallationGuideECLComfort310,applicationA361
PheatT(heatdemand)
11078
CircuitSettingrange
Factorysetting
1
5...40°C20°C
Whenthedesiredowtemperatureisabovethesettemperaturein‘PheatT’ ,
thecontrollerautomaticallyswitchesONthecirculationpump.
5...40:
Frostpr.T(frostprotectiontemperature)
11093
CircuitSettingrange
Factorysetting
1
5...40°C10°C
Setthedesiredowtemperatureforexampleatheatingcut-out,totalstop
etc.toprotectthesystemagainstfrost.