Installation guide
InstallationGuideECLComfort210/310,applicationA231/A331
5.9Alarm
5.9.1Temp.monitor.
Upperdifference
11147
CircuitSettingrange
Factorysetting
1
OFF/1...30KOFF
Thealarmisactivatediftheactualowtemperatureincreasesmorethan
thesetdifference(acceptabletemperaturedifferenceabovethedesired
owtemperature).Seealso'Delay'.
OFF:
1...30K:
Flowtemp.°C
Upperdifference(set
value)
Desiredowtemp.
Outdoortemp.
°C
Lowerdifference
11148
CircuitSettingrange
Factorysetting
1
OFF/1...30KOFF
Thealarmisactivatediftheactualowtemperaturedecreasesmorethan
thesetdifference(acceptabletemperaturedifferencebelowthedesired
owtemperature).Seealso'Delay'.
OFF:
1...30K:
Flowtemp.°C
Lowerdifference(set
value)
Desiredowtemp.
Outdoortemp.
°C