Installation guide

InstallationGuideECLComfort210/310,applicationA231/A331
5.8Application
Demandoffset
11017
CircuitSettingrange
Factorysetting
1
OFF/1...20KOFF
Thedesiredowtemperatureinheatingcircuit1canbeinuencedbythe
demandforadesiredowtemperaturefromanothercontroller(slave)or
anothercircuit.
OFF:



1...20:

 

Temp.
Settingin
‘Demandoffset’
Des.owtemp.,
circuit1
Des.owtemp.,
circuit2
Time


Mexercise(valveexercise)
11023
CircuitSettingrange
Factorysetting
1
OFF/ONOFF
Exercisesthevalvetoavoidblockinginperiodswithoutheatdemand.
OFF:

ON:


DHWpriority(closedvalve/normaloperation)
11052
CircuitSettingrange
Factorysetting
1
OFF/ONOFF
Theheatingcircuitcanbeclosedwhenthecontrolleractsasslaveandwhen
DHWchargingisactiveinthemaster.
OFF:


ON:


*Thedesiredowtemperatureissettothevaluesetin
‘Frostpr.T’

PfrostT
11077
CircuitSettingrange
Factorysetting
1
OFF/-10...20°C2°C
Whentheoutdoortemperatureisbelowthesettemperaturein‘PfrostT’ ,
thecontrollerautomaticallyswitchesONthecirculationpumptoprotect
thesystem.
OFF:

-10...20:







