Installation guide
InstallationGuideECLComfort210/310,applicationA231/A331
Change,duration
11311
CircuitSettingrange
Factorysetting
1
1...102
Thenumberofdaysbetweenshiftofcirculationpumps.Theshifttakesplace
atthetimesetin'Changetime'.
ON
OFF
ON
OFF
P3
P5
P3
P3
P3
P5
P5
P5
Days
Changetime(changeovertime)
11312
CircuitSettingrange
Factorysetting
1
0...2312
Theexacttimeoftheday,wheretheshiftmusttakeplace.Thedayisdivided
into24hours.Thefactorysettinghereis12whichmeans12:00(noon).
ON
OFF
ON
OFF
P3
P5
P3
P5
Time
1day
Pexercise(pumpexercise)
11022
CircuitSettingrange
Factorysetting
1
OFF/1...200sOFF
Thetimethepumpisactivatedduringexercise.Exercisetakesplaceevery
day(at12:20)whennoheatdemandhasbeenpresent.
OFF:
1...200:
Example:
OFF:
ON: