Installation guide
InstallationGuideECLComfort210/310,applicationA231/A331
HighlimitY2(returntemp.limitation,highlimit,Y-axis)
11034
CircuitSettingrange
Factorysetting
1
10...150°C60°C
Setthereturntemperaturelimitationreferringtotheoutdoortemperature
setin'LowToutX2'.
In.-max.(returntemp.limitation-max.inuence)
11035
CircuitSettingrange
Factorysetting
1
-9.9...9.90.0
Determineshowmuchthedesiredowtemperaturewillbeinuencedifthe
returntemperatureishigherthanthecalculatedlimit.
Inuencehigherthan0:
Inuencelowerthan0:
Example
In.-min.(returntemp.limitation-min.inuence)
11036
CircuitSettingrange
Factorysetting
1
-9.9...9.90.0
Determineshowmuchthedesiredowtemperaturewillbeinuencedifthe
returntemperatureislowerthanthecalculatedlimit.
Inuencehigherthan0:
Inuencelowerthan0:
Example
Adapt.time(adaptationtime)
11037
CircuitSettingrange
Factorysetting
1
OFF/1...50s
25s
Controlshowfastthereturntemperatureadaptstothedesiredreturn
temperaturelimit(Icontrol).
OFF:
1:
50: