Installation guide
InstallationGuideECLComfort210/310,applicationA231/A331
5.2Returnlimit
Returntemperaturelimitation
HighlimitY2
LowlimitY1
° C
15
40
-15
60
° C
Outdoortemp.
LowToutX2
HighToutX1
Inuence
‘In.-min. ’>0
‘Limit’
‘In.-max. ’>0
Returntemperature
‘In.-max. ’<0
‘In.-min. ’<0
HighToutX1(returntemp.limitation,highlimit,X-axis)
11031
CircuitSettingrange
Factorysetting
1
-60...20°C15°C
Settheoutdoortemperatureforthelowreturntemperaturelimitation.
LowlimitY1(returntemp.limitation,lowlimit,Y-axis)
11032
CircuitSettingrange
Factorysetting
1
10...150°C40°C
Setthereturntemperaturelimitationreferringtotheoutdoortemperature
setin'HighToutX1'.
LowToutX2(returntemp.limitation,lowlimit,X-axis)
11033
CircuitSettingrange
Factorysetting
1
-60...20°C-15°C
Settheoutdoortemperatureforthehighreturntemperaturelimitation.