Theauxiliaryheaterismadeupofanelectricheatingelementonthesupplypipethathastwooutputs,ADD.HEAT1andADD.HEAT2,
andcanbecontrolledinthreesteps:
Forthreephase,400V,installations:
• Step1=ADD.HEAT1=3kW
• Step2=ADD.HEAT2=6kW
• Step3=ADD.HEAT1+ADD.HEAT2=9kW
Forsinglephase,230V,installations:
• Step1=ADD.HEAT1=1.5kW
• Step2=ADD.HEAT2=3kW
• Step3=ADD.HEAT1+ADD.HEAT2=4.5kW
Intheeventofanalarm,theauxiliaryheaterengagesautomatically.
Theenergyconsumptioncalculationisdifficulttospecifyexactly,buttheaverageoutputforanormalhousewithnormalhotwater
consumptioninthefollowingtablesgivesarelativelyaccurateresultforeachheatpumpandheatingsystem.Rememberthatthe
operatingtimefortheheatpumpinstallationmustexceedoneyearbeforethespecifiedvaluesinthetablearevalid.
TheenergyconsumptionforlegionoperationisincludedinthehoursforADD.HEAT1.
Theindicatedoutputsincludecirculationpumps.
DHP-H -4 -6 -8 -10 -12 -16
Underfloorheating 1.13kW 1.59kW 2.00kW 2,55kW 2.90kW 4.31kW
Radiators 1.39kW 1.88kW 2.36kW 3.03kW 3.43kW 5.11kW
Tocalculatetheenergyconsumption:
1 PresseithertherightorleftbuttononcetoopentheINFORMATIONmainmenu.ThecursorisintheOPERATIONmenuoption.
2 PressthedownbuttontomovethecursortotheOPERAT.TIMEmenuoption.
3 Openthemenubypressingtherightbuttononce.
4 Notehowmanyhoursthefollowingvalueshave:HEATPUMP,ADD.HEAT1,andADD.HEAT2.
5 Inthetablesabovefindthevaluefortheaverageoutputthatcorrespondstoyourheatpumpandheatingsystem,andmultiplyitby
thenumberofHEATPUMPhours.Notetheresult.
6 MultiplythenumberofADD.HEAT1hoursby3.Notetheresult.
7 MultiplythenumberofADD.HEAT2hoursby6.Notetheresult.
8 Addupthemultipliedvaluestoobtainthetotalenergyconsumption.
Auxiliary heating and energy consumption calculation