Specifications

60 – Service VMBMH302
Problem – irregular indoor temperature
Cause Troubleshooting Remedy
1. The heat pumps control com-
puter is not set/adjusted to the
customer’s requirements/wishes.
Check the ROOM and CURVE, MIN, MAX
CURVE5, CURVE0, CURVE-5 and HEAT
STOP settings.
Adjust incorrect values in the heat pumps
control computer.
ROOM = Desired indoor temperature
CURVE = Should be set so that the desired
indoor temperature (ROOM) is maintained
regardless of the outdoor temperature.
MIN = Lowest set-point value on the
supply line regardless of the outdoor tem-
perature (on the condition that heat stop
does not apply).
MAX = Highest set-point value on the
supply line regardless of the outdoor tem-
perature.
CURVE5,0,-5 = The supply temperature
can be adjusted up or down 5°C at these
outdoor temperatures.
HEAT STOP = Stops all production of heat
when the outdoor temperature is the
same as or greater than the set value. To
exit heat stop the outdoor temperature
must drop to 3°C below the set value.
2. Incorrectly positioned/instal-
led sensors.
Check that outdoor sensors and any
room sensors are installed according to
the instructions and that they are cali-
brated.
Check that the room sensor is positioned in
a suitable place that is representative of the
building and calibrate it if necessary. Avoid
placing near external doors, windows and
heat sources.
Install the outdoor sensor according to the
instructions and calibrate it, if necessary.
15.4.6 Other
Problem – The heat pump runs and runs but never stops
Cause Troubleshooting Remedy
1. Air in the heating system. Listen for air in the heat pump and hea-
ting system.
Bleed the heating system according to
the installation instructions.
2. Lack of refrigerant, not enough
refrigerant in the system.
Using manometer apparatus and ther-
mometer, check that the unit’s overhea-
ting is correct for the specific refrigerant.
Follow the correct procedure (depending
on type of refrigerant) to add the correct
amount of refrigerant.
If there appears to be a leak in the refri-
gerant circuit, carry out leak tracing and
any necessary corrective action. If leak
tracer is not available, brush soap water
on the suspected leak and look for bubb-
les. Also check for oil as this can come
out from the refrigerant circuit.
3. Changed conditions Have you
increased your heating and/or
hot water demand?
• If the heat pump has been dimensioned
for a certain demand and this demand is
increased, the heat pump might not be
able to maintain the desired room tem-
perature.
• If hot water consumption increases,
a larger proportion of time is used to
produce hot water, which means less
time for heat production (only applies to
VL-systems).
If the heat pump cannot cope with the
demand, replace it with one with a hig-
her output or supplement it with a hig-
her output auxiliary heater.