Datasheet
Technical specification DHP-AQ
Produced by Danfoss A/S © 2011-02-14
2
VDGFE102
The measurements are performed on a limited number of heat
pumps which can cause variations in the results. Tolerances in the
measuring methods can also cause variations.
1) At A7/W35 Δ10K warm side. (EN 255)
2) At A7/W35 according to EN 14511.
3) At A35/W7 according to EN14511.
4) Nominal flow: heating circuit Δ10K.
5) At outdoor temperature 0°C
6) According to SS-EN 12102, EN ISO 3741.
7) The values apply to a new heat pump with clean heat
exchangers.
8) Under test
Indoor kit
Mini: controller
Midi: controller, circulation pump (class A), auxiliary heater (400V - 3/6/9/12/15 kW; 230V - 3/6/9 kW), three way valve
Maxi: controller, hot water tank (180 l), circulation pump (class A), auxiliary heater (400V - 3/6/9/12/15 kW; 230V -3/6/9 kW),
three way valve
DHP-AQ
6 9 11 13 16 18
Refrigerant
Type R407C R407C R407C R407C R407C R407C
Amount kg 4.3 4.3 5.0 5.0 5.7 6.0
Test pressure MPa 3.4 3.4 3.4 3.4 3.4 3.4
Design pressure MPa 3.1 3.1 3.1 3.1 3.1 3.1
Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll
Oil POE POE PVE POE PVE POE
Electrical data
3-N, ~50Hz
Main supply Volt 400 400 400 400 400 400
Rated power, compressor kW 2.2 2.9 3.3 4.2 5 6.1
Rated power, fan kW 0.2 0.2 0.2 0.3 0.3 0.7
Start current A 12 10 18 17 UT
8
18
Fuse A 10 10 16 16 16 16
Electrical data
1-N, ~50Hz
Main supply Volt 230 230 230 230 230 -
Rated power, compressor kW 2.4 2.8 3.6 4.3 5.5 -
Rated power, fan kW 0.2 0.2 0.2 0.3 0.3 -
Start current A 11 21 26 28 39 -
Fuse A 20 20 32 32 40 -
Performance
7
COP
1
4.1 4.6 4.6 4.3 4.4 4.0
COP
2
4.0 4.4 4.3 4.3 4.2 3.9
Heating capacity
2
kW 6.2 8.6 10.8 12.2 15.3 17.9
Power input - heating
2
kW 1.5 2.0 2.5 2.9 3.7 4.6
EER
3
2.2 2.4 2.3 2.3 2.3 2.1
Cooling capacity
3
4.3 5.9 7.4 8.6 10.0 11.4
Power input - cooling
3
1.9 2.5 3.2 3.7 4.4 5.4
Nominal flow
4
Heating circuit l/s 0.150 0.216 0.263 0.299 0.372 0.432
Operating range (outdoor)
°C -20~+45°C -20~+45°C -20~+45°C -20~+45°C -20~+45°C -20~+45°C
Max temperature
5
Heating circuit °C 60 60 60 60 60 60
Pressure levels
Low pressure MPa 0.05 0.05 0.05 0.05 0.05 0.05
Operating MPa 2.85 2.85 2.85 2.85 2.85 2.85
High pressure MPa 3.1 3.1 3.1 3.1 3.1 3.1
Sound power level
Regular mode
6
dB(A) 61 62 64 66 66 74
Silent mode
6
dB(A) 58 59 61 63 63 71
Weight
Outdoor unit kg 125 131 150 155 191 185
Mini kg 18 18 18 18 18 18
Midi kg 21 21 21 21 21 21
Maxi kg 106 106 106 106 106 106
Outdoor unit Width x Depth x Height mm 856x510x1272 856x510x1272 1016x564x1477 1016x564x1477 1166x570x1557 1166x570x1557
Mini (Indoor kit) Width x Depth x Height mm 380x204x600
Midi (Indoor kit) Width x Depth x Height mm 420x255x625 (+50mm pipes)
Maxi (Indoor kit) Width x Depth x Height mm 596x690x1845 ±10
Connections:
1. Supply line heating system (all sizes) - 28 mm Cu
2. Return line heating system (all sizes) - 28 mm Cu
Mini
Maxi
Midi
DHP-AQ front view DHP-AQ rear view
1
2
Danfoss assumes no responsibility for any errors found in the catalogues, brochures and any other printed material. Danfoss retains the right to make changes to their products, including products that have
already been ordered, without prior notice, as long as these changes can be carried out without changing predetermined specifications. All trademarks in this material belong to respective companies. Danfoss
and the Danfoss logo are trademarks that belong to Danfoss A/S. All rights reserved.