Datasheet
Technical specication Danfoss DHP-AQ
The measurements are performed on a limited number of heat pumps which
can cause variations in the results. Tolerances in the measuring methods can
also cause variations.
1) At A7/W35 Δ10K warm side. (EN 255)
2) At A7/W35 according to EN 14511.
3) At A35/W7 according to EN14511.
4) Nominal flow: heating circuit Δ10K.
5) At outdoor temperature 0°C
6) According to SS-EN 12102, EN ISO 3741.
7) According to ISO 11203, cuboid-shaped measuring surface
8) The values apply to a new heat pump with clean heat exchangers.
*) The Swedish Energy Agency has conducted an extensive test of air/water heat pumps. The new Danfoss DHP-AQ has the best annual efficiency, and consequently delivers the biggest savings. Test performed by the Swedish Energy Agency has been
announced September 2011. More information you can find on http://www.energimyndigheten.se/sv/Hushall/Testerresultat/Testresultat/Luftvattenvarmepumpar1/?tab=2
DHP-AQ
6 9 11 13 16 18
Refrigerant
Type R407C R407C R407C R407C R407C R407C
Amount kg 4.0 4.3 5.0 5.1 5.7 6.0
Design pressure MPa 3.1 3.1 3.1 3.1 3.1 3.1
Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll
Oil POE POE POE POE POE POE
Electrical data
3-N, ~50Hz
Main supply Volt 400 400 400 400 400 400
Rated power, compressor kW 2.2 2.9 3.3 4.2 5.0 6.1
Rated power, fan kW 0.2 0.2 0.2 0.3 0.3 0.7
Start current A 12 10 18 17 18 18
Fuse A 10 10 16 16 16 16
Electrical data
1-N, ~50Hz
Main supply Volt 230 230 230 230 230 -
Rated power, compressor kW 2.4 2.8 3.6 4.3 5.5 -
Rated power, fan kW 0.2 0.2 0.2 0.3 0.3 -
Start current A 11 21 26 28 38 -
Fuse A 20 20 25 32 32 -
Performance
8
COP
1
4.7 4.7 5.0 4.7 4.6 4.3
COP
2
4.3 4.4 4.7 4.4 4.1 4.0
Heating capacity
2
kW 6.5 8.6 11.1 12.3 15.2 17.6
Power input - heating
2
kW 1.5 2.0 2.4 2.8 3.7 4.4
EER
3
2.2 2.4 2.5 2.4 2.3 2.3
Cooling capacity
3
4.2 5.9 7. 5 8.9 10.4 13.1
Power input - cooling
3
1.9 2.5 3.0 3.7 4.5 5.7
Nominal ow
4
Heating circuit l/s 0.150 0.216 0.263 0.299 0.372 0.432
Operating range (outdoor) °C -20~+45°C -20~+45°C -20~+45°C -20~+45°C -20~+45°C -20~+45°C
Max temperature
5
Heating circuit °C 60 60 60 60 60 60
Pressure levels
Low pressure MPa 0.05 0.05 0.05 0.05 0.05 0.05
Operating MPa 2.85 2.85 2.85 2.85 2.85 2.85
High pressure MPa 3.1 3.1 3.1 3.1 3.1 3.1
Sound power level
Regular mode
6
dB(A) 61 61 61 62 66 76
Low noise mode
6
dB(A) 60 59 60 61 64 71
Sound pressure level
(1 meter)
Regular mode
7
dB(A) 46 46 46 47 51 61
Low noise mode
7
dB(A) 45 44 44 46 48 55
Weight
Outdoor unit kg 125 131 150 155 185 191
Mini kg 18 18 18 18 18 18
Midi kg 21 21 21 21 21 21
Maxi kg 106 106 106 106 - -
Outdoor unit Width x Depth x Height mm 856x510x1272 856x510x1272 1016x564x1477 1016x564x1477 1166x570x1557 1166x570x1557
Mini (Indoor kit) Width x Depth x Height mm 380x204x600
Midi (Indoor kit) Width x Depth x Height mm 420x255x625 (+50mm pipes)
Maxi (Indoor kit) Width x Depth x Height mm 596x690x1845 ±10 - -
Connection heat pump
1
Supply line heating system (all sizes) - 28 mm Cu
2
Return line heating system (all sizes) - 28 mm Cu
Indoor kit
Mini: controller
Midi: controller, circulation pump (class A), auxiliary heater
(400V - 3/6/9/12/15 kW; 230V - 3/6/9 kW), three way valve
Maxi: controller, hot water tank (180 l), circulation pump (class A),
auxiliary heater (400V - 3/6/9/12/15 kW; 230V -3/6/9 kW),
three way valve
Mini
Maxi
Midi
1
2
VDGFE302
Produced by Danfoss A/S March 2012
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order
provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the
Danfoss logotype are registered trademarks of Danfoss A/S. All rights reserved