Installation guide
AKC 24A Version 1.0x Menu operation RC.1N.H1.02 © Danfoss 06/96 7
|
Manual Control Forced servo operation of outlets (service)
>>
5:02
Man. Ctrl. ON: Manual setting allowed (se 2:02:01)
OFF ON PLEASE NOTE: No monitoring
5:02:01 When manual setting has been completed, setting must be changed to OFF
|
AKV 1 % Forced servo operation of the expansion valve
0 100
5:02:02
|
AKV 2 % Forced servo operation of the expansion valve
0 100
5:02:03
|
AKV 3 % Forced servo operation of the expansion valve
0 100
5:02:04
|
DO1 Forced servo operation of outlet
OFF ON On = normal Off = alarm
5:02:05
|
DO2 Forced servo operation of outlet
OFF ON On = normal Off = alarm
5:02:06
|
DO3 Forced servo operation of outlet
OFF ON On = normal Off = alarm
5:02:07
|
Alarm Relay Forced servo operation of alarm relay outlet
OFF ON On = normal Off = alarm
5:02:08