Operating instructions

Table Of Contents
6.1.3 Testing the system pump
1. Enable the system pump by pressing (manual enable).
2. Start the system pump by pressing (on/off).
3. Check that the system pump is running by:
listening
placing a hand on the pump
listening for air
4. Bleed the system if necessary. See chapter 'Filling and bleeding the water heater and heating system'
5. Stop the system pump by pressing .
6.1.4 Testing the compressor
1. Enable the compressor by pressing (manual enable).
2. Set compressor gear.
3. Check that there is no abnormal noise.
4. Check that the pressure pipe becomes hot.
5. Stop the compressor by pressing
(manual enable).
6.1.5
Exiting manual test
To exit manual test:
1. Press on the Start screen to open the Menu screen.
2.
Press on Settings
.
3.
Press to go to the menu page for Manual test.
4. Press on the text Manual test.
5. Press to exit manual test.
The
symbol disappears.
6.1.6
Insulating pipes
When the manual test is completed, a check for leaks should be carried out. When the leakage check has been successfully completed,
the pipes should be insulated.
Caution Ensure that the pipes which transport cold water are properly insula-
ted to prevent condensation damage.
Commissioning DHP-M
Danfoss Heating Solutions VIJSE302
25