User`s guide

The grey
side of the
ECL Card
Extended service
32p
Service parameter(s) 80-140
80 Anti-bacteria function period
Circuit Setting range Factory setting
(I) / (II) 5 ... 250 min. 120 min.
Set the period for the anti-bacteria function. When the set time
expires, the anti-bacteria function is stopped.
5 ... 250:
The anti-bacteria function is active for the
set period.
The function is activated in line 78 by setting the desired anti-
bacteria temperature.
83 Daily / weekly anti-bacteria function
Circuit Setting range Factory setting
I ON / OFF ON
Choose whether the anti-bacteria function is to be active daily or
weekly.
ON: The anti-bacteria function is active once a
day (from 00:00).
OFF: The anti-bacteria function is active once a
week (Mondays from 00:00).
140 Function of temperature sensor S5
Circuit Setting range Factory setting
I 0, 1, 2 0
Sensor S5 can be used optionally as return temperature sensor
in circuit II (limitation of the return temperature), as lower DHW
tank temperature sensor (cut-out temperature) or as DHW
charging temperature sensor.
0: Return temperature sensor, circuit II.
1: Lower DHW tank temperature sensor.
2: DHW charging temperature sensor (system
types 5 and 5a).